Siemens Germany · Combined cycle
Used Siemens V94.2 combined cycle power plant of about 200 MW at 50 Hz, in a 1 GT + 1 HRSG + 1 ST multi-shaft arrangement, manufactured in 1991 and commissioned in 1992. The gas turbine is rated 143.3 MW at ISO conditions (dual fuel, about 115,000 OH / 127,400 EOH and 700 starts) and the Skoda steam turbine is rated 60 MWe. One complete block is available, installed, in Europe.
This listing is for one used Siemens V94.2 combined cycle block of about 200 MWe at 50 Hz, in a 1 GT + 1 HRSG + 1 ST multi-shaft arrangement. The plant was manufactured in 1991 and commissioned in 1992, and is offered used and maintained. One complete CCGT block is available, currently installed, in Europe, and may be sold as a complete block or by major components.
The gas turbine is a Siemens V94.2 heavy-duty unit rated 143.3 MW at ISO conditions, upgraded from a pre-ratio to a ratio turbine section with HR3 premix burners. It is dual fuel (natural gas and fuel oil) and has an inlet fogging system for power augmentation. Recorded operating time is about 115,000 OH / 127,400 EOH with 700 starts. Two major overhauls have been completed, with the rotor de-stacked on each occasion, and a lifetime extension at about 96,000 EOH included hot-gas-path blading, the turbine upgrade and the HR3 combustion upgrade. The GT generator is a Siemens TLRI 108/46, 185 MVA, 15.75 kV, 0.8 power factor, air-cooled.
The steam side is a vertical, forced-circulation, single-pressure heat-recovery steam generator (about 17 bar / 310 °C / 303 t/h) with no bypass stack, so the gas turbine operates in combined-cycle mode only, together with a Skoda steam turbine of 60 MWe nominal with a low-pressure inlet (about 16 bar, 310 °C) driving a Skoda 80 MVA, 10.5 kV, 0.85 power factor, air-cooled generator. Electrical plant includes a 40/30/10 MVA, 15.75/10.5/6.3 kV GT unit auxiliary transformer, for a 132 kV grid connection. The generator step-up transformers are offered separately as standalone listings. The technical information pack and photos are attached.
| Parameter | Details |
|---|---|
| Plant Type | Combined cycle, 1 GT + 1 HRSG + 1 ST, multi-shaft, about 200 MWe |
| Manufacturer / Model | Siemens V94.2 (steam turbine: Skoda) |
| Year of Manufacture | 1991 (commissioned 1992) |
| Rated Output | About 200 MWe combined cycle (GT 143.3 MW ISO + ST 60 MWe) |
| Frequency | 50 Hz |
| Fuel | Dual fuel: natural gas / fuel oil |
| Gas Turbine | Siemens V94.2 heavy-duty, 50 Hz, 143.3 MW at ISO conditions |
| GT Upgrades | Pre-ratio to ratio turbine section; HR3 premix burner upgrade |
| Inlet | Fogging system for power augmentation |
| GT Operating Hours | About 115,000 OH / 127,400 EOH |
| GT Starts | 700 |
| GT Maintenance | Two major overhauls (rotor de-stacked each time); lifetime extension at about 96,000 EOH including hot-gas-path blading, turbine upgrade and HR3 combustion |
| GT Generator | Siemens TLRI 108/46, 185 MVA, 15.75 kV, 0.8 PF, air-cooled |
| HRSG | Vertical, forced circulation, single pressure; about 17 bar / 310 °C / 303 t/h; no bypass stack (combined-cycle operation only) |
| Steam Turbine | Skoda, 60 MWe nominal, low-pressure inlet (about 16 bar, 310 °C) |
| ST Generator | Skoda, 80 MVA, 10.5 kV, 0.85 PF, air-cooled |
| GT Unit Auxiliary Transformer | 40/30/10 MVA, 15.75/10.5/6.3 kV |
| Grid Connection | 132 kV |
| Condition | Used, maintained, currently installed |
| Availability | 1 complete CCGT block (sale as a complete block or by major components) |
| Location / Terms | Europe |
| System | Equipment |
|---|---|
| Gas Turbine | Siemens V94.2 gas turbine with fuel-gas and fuel-oil systems |
| Inlet | GT inlet air system with fogging |
| GT Generator | Siemens TLRI 108/46 generator (185 MVA) with excitation |
| GT Auxiliary Transformer | GT unit auxiliary transformer (40/30/10 MVA, 15.75/10.5/6.3 kV) |
| HRSG | Heat-recovery steam generator (single pressure) with stack; no bypass stack |
| Steam Turbine | Skoda steam turbine (60 MWe) |
| ST Generator | Skoda ST generator (80 MVA, 10.5 kV) |
| Controls | GT/ST control and protection systems |
| Balance of Plant | Balance-of-plant auxiliaries |
| Offer Basis | Option to sell as a complete block or by major components |
If you require any further information on this listing please contact info@reflowx.com