Used GANZ DHM 180000/132 three-phase, oil-immersed, two-winding power transformer, rated 180 MVA at 50 Hz with a 132/15.75 kV voltage ratio. Manufactured and commissioned in 1990, it is a generator step-up unit with OFAF cooling, currently installed. One unit is available, in Europe.
This is a used GANZ DHM 180000/132 three-phase, oil-immersed, two-winding power transformer, rated 180 MVA at 50 Hz with a 132 / 15.75 kV voltage ratio. It was manufactured and commissioned in 1990 and is offered used. One unit is available, currently installed, in Europe.
The transformer is arranged as a generator step-up (GSU) unit, vector group YNd11, with a short-circuit impedance of 11.6%. Cooling is OFAF (forced oil, forced air). Rated current is 787 / 6,598 A. No-load losses are 103.6 kW and load losses are 541.5 kW. Total weight is 162.5 t, with a transport weight of 143 t, a lifting weight of 105 t and about 25 t of insulating oil in the main tank.
The scope of supply is the complete main transformer (active part and tank) with HV, LV and neutral bushings, conservator with breather, OFAF cooling equipment (coolers, oil pumps and fans), a tap changer, insulating oil, protection devices (Buchholz, PRD and temperature indicators), a marshalling / control cabinet, and original drawings and test documentation. The technical information pack and photo are attached.
| Parameter | Details |
|---|---|
| Manufacturer / Model | GANZ DHM 180000/132 |
| Type | Three-phase, oil-immersed, two-winding power transformer |
| Rated Power | 180 MVA |
| Rated Voltage | 132 / 15.75 kV |
| Rated Current | 787 / 6,598 A |
| Frequency | 50 Hz |
| Vector Group | YNd11 |
| Short-circuit Impedance | 11.6% |
| Cooling | OFAF (forced oil, forced air) |
| No-load Losses | 103.6 kW |
| Load Losses | 541.5 kW |
| Typical Application | Generator step-up (GSU) |
| Year of Manufacture | 1990 (commissioned 1990) |
| Total Weight | 162.5 t |
| Transport Weight | 143 t |
| Lifting Weight | 105 t |
| Oil in Main Tank | About 25 t |
| Condition | Used, currently installed |
| Availability | 1 unit available |
| Location / Terms | Europe |
| System | Equipment |
|---|---|
| Main Transformer | 1 × GANZ DHM 180000/132 active part and tank |
| Bushings | HV, LV and neutral bushings |
| Conservator | Conservator with breather |
| Cooling | OFAF cooling equipment (coolers, oil pumps, fans) |
| Tap Changer | Tap changer (type and range not stated in the pack) |
| Insulating Oil | About 25 t in the main tank |
| Protection | Buchholz, PRD and temperature indicators |
| Controls | Marshalling / control cabinet |
| Documentation | Original drawings and test documentation |