- Home/
- Electrical Grid/
- Power Step Up Transformers/
- CHINT 50/60 MVA On Load Tap Changing Power Transformer – 132/11 kV – 50 Hz – 2016
Description
This CHINT power transformer is an oil-immersed, three-phase, two-winding unit rated 50/60 MVA (ONAN / ONAF) at 50 Hz, with a 132 kV high-voltage winding and an 11 kV low-voltage winding, vector group YNd1. It was manufactured in 2016 and is offered used, with one unit available.
The HV side has an on-load tap changer covering approximately 118.8 kV to 145.25 kV in 17 positions. Rated currents are about 218 A (HV) and 2,624 A (LV) on a 50 MVA basis, with insulation levels of LI 550 / AC 200 kV on the HV side and AC 42 kV on the LV side. Cooling is ONAN / ONAF with detachable radiator banks and a fan bank in a dedicated cooling cabinet.
The transformer is in outdoor storage. The scope includes the tank with core and windings, HV and LV porcelain bushings, the OLTC with drive, conservator with Buchholz relay, temperature indicators, radiators, forced-air cooling cabinet, marshalling kiosk and insulating oil. The technical information pack and photos are attached.
Specifications
| Parameter | Details |
|---|---|
| Manufacturer / Model | CHINT Electric, on-load tap-changing power transformer |
| Type | Oil-immersed, three-phase, two-winding power transformer |
| Rated Capacity | 50/60 MVA (ONAN / ONAF) |
| Rated Voltage | HV 132 kV / LV 11 kV |
| Frequency | 50 Hz |
| Vector Group | YNd1 |
| Tap Changer | On-load tap changer (OLTC), HV side, about 118.8 kV to 145.25 kV in 17 positions |
| Rated Current | HV about 218 A; LV about 2,624 A (50 MVA basis) |
| Insulation Level | HV LI 550 / AC 200 kV; MV LI 230 / AC 95 kV; LV AC 42 kV |
| Cooling | ONAN / ONAF; detachable panel radiator banks, separate fan / control cabinet |
| Bushings | Porcelain, HV and LV, with OLTC compartment |
| Year of Manufacture | 2016 |
| Condition / Availability | Used; outdoor storage; 1 unit available |
Scope of Supply
| System | Equipment |
|---|---|
| Active Part | Main tank with core and windings (HV 132 kV, LV 11 kV) |
| Bushings | HV bushings and LV bushings |
| Tap Changer | On-load tap changer (OLTC) with drive mechanism |
| Oil System | Conservator and oil level indication; Buchholz / gas accumulation relay; insulating oil |
| Monitoring | Winding temperature indicator and oil temperature indicator |
| Cooling | Radiator banks, both sides, with isolating valves; forced-air cooling cabinet with fans and control |
| Control | Local marshalling / control cabinet |
| Mechanical | Jacking / skid rails; earthing terminals; nameplates |
If you require any further information on this listing please contact info@reflowx.com
Supporting Documents
General Terms
- ReflowX and the seller retain the right to evaluate and approve offers.
- Buyers should verify quantities and conditions upon delivery.
- After successful engagement, both buyer and seller manage communication for payment terms and delivery schedule.
- All parties agree to adhere to ReflowX Terms and Conditions in transactions.
- Buyers can request value-added services such as pre-purchase inspections, Expediting & Delivery Services through ReflowX. Contact us!