This CHINT power transformer is an oil-immersed, three-phase, two-winding unit rated 50/60 MVA (ONAN / ONAF) at 50 Hz, with a 132 kV high-voltage winding and an 11 kV low-voltage winding, vector group YNd1. It was manufactured in 2016 and is offered used, with one unit available.

The HV side has an on-load tap changer covering approximately 118.8 kV to 145.25 kV in 17 positions. Rated currents are about 218 A (HV) and 2,624 A (LV) on a 50 MVA basis, with insulation levels of LI 550 / AC 200 kV on the HV side and AC 42 kV on the LV side. Cooling is ONAN / ONAF with detachable radiator banks and a fan bank in a dedicated cooling cabinet.

The transformer is in outdoor storage. The scope includes the tank with core and windings, HV and LV porcelain bushings, the OLTC with drive, conservator with Buchholz relay, temperature indicators, radiators, forced-air cooling cabinet, marshalling kiosk and insulating oil. The technical information pack and photos are attached.

Specifications

ParameterDetails
Manufacturer / ModelCHINT Electric, on-load tap-changing power transformer
TypeOil-immersed, three-phase, two-winding power transformer
Rated Capacity50/60 MVA (ONAN / ONAF)
Rated VoltageHV 132 kV / LV 11 kV
Frequency50 Hz
Vector GroupYNd1
Tap ChangerOn-load tap changer (OLTC), HV side, about 118.8 kV to 145.25 kV in 17 positions
Rated CurrentHV about 218 A; LV about 2,624 A (50 MVA basis)
Insulation LevelHV LI 550 / AC 200 kV; MV LI 230 / AC 95 kV; LV AC 42 kV
CoolingONAN / ONAF; detachable panel radiator banks, separate fan / control cabinet
BushingsPorcelain, HV and LV, with OLTC compartment
Year of Manufacture2016
Condition / AvailabilityUsed; outdoor storage; 1 unit available

Scope of Supply

SystemEquipment
Active PartMain tank with core and windings (HV 132 kV, LV 11 kV)
BushingsHV bushings and LV bushings
Tap ChangerOn-load tap changer (OLTC) with drive mechanism
Oil SystemConservator and oil level indication; Buchholz / gas accumulation relay; insulating oil
MonitoringWinding temperature indicator and oil temperature indicator
CoolingRadiator banks, both sides, with isolating valves; forced-air cooling cabinet with fans and control
ControlLocal marshalling / control cabinet
MechanicalJacking / skid rails; earthing terminals; nameplates

 

If you require any further information on this listing please contact info@reflowx.com

Supporting Documents

General Terms

  • ReflowX and the seller retain the right to evaluate and approve offers.
  • Buyers should verify quantities and conditions upon delivery.
  • After successful engagement, both buyer and seller manage communication for payment terms and delivery schedule.
  • All parties agree to adhere to ReflowX Terms and Conditions in transactions.
  • Buyers can request value-added services such as pre-purchase inspections, Expediting & Delivery Services through ReflowX. Contact us!

Similar Products in

Reflowx icon

ReflowX - A Trusted Marketplace for Surplus Energy Sector Equipment

Shape a sustainable and circular future while reducing costs and carbon emissions with us.

  • ✅ Free Listings, No Hidden Fees
  • ✅ Low-Cost Procurement
  • ✅ Cost Recovery Solutions
  • ✅ Tailored Sales Support
App StoreGoogle Play
Mobile App